Exit emergency lights are often overlooked and sometimes go without maintenance until the State or local inspections are performed and fines are looming. JW Kennedy understands the importance of including these unit inspections as part of your Annual Fire Protection services. We are well versed in the diversity of battery configuration and the requirements needed for your equipment to work as needed.

Exit emergency light requirements are outlined in NFPA 101, Life Safety Code. This code requires emergency lighting to be provided in designated stairs, aisles, corridors and passageways leading to an exit in commercial properties such as, but not limited to, hospitals, schools, churches, hotels, businesses and places of assembly. The markings of emergency lighting need to be visible from any direction of the exit access and are required to be internally or externally illuminated. The illumination of the exit marking needs to be confirmed by a visual inspection at intervals not exceeding 30 days. If the occupancy is also required to have emergency lighting, these illuminated exit signs need to be provided with emergency power. The same methods of testing the emergency lighting can be used for testing the exit marking illumination emergency power as well.

NFPA 101 requires emergency and illuminated signs to turn on automatically during a power failure and stay lit for 90 minutes.

Core Illumination Requirements

  • Duration: Must operate for a minimum of 90 minutes on battery backup or an emergency generator.
  • Light Level: Must provide an average of at least 1 foot-candle and a minimum of 0.1 foot-candle at any point along the floor of the egress path, to be determined at installation; not verified during an inspection.
  • Activation: Must trigger automatically upon utility power loss, tripped breakers, or switched off normal lighting circuits.

Placement & Location

  • Pathways: Required along all designated exit access corridors, stairs, ramps, and passageways leading to an exit.
  • Key Points: Must be positioned at every exit door, change in floor level, corridor intersection, and directional run.

Exit Sign Standards

  • Visibility: Exit signs must be clearly visible, illuminated 24/7, and backed by 90-minute emergency power.
  • Testing: Systems require a functional test every 30 days and a full 90-minute annual test.

Proper documentation is required with these tests to verify all the work was done and to ensure that no required testing is overlooked.

Why a System Can Fail

A system can fail for the following reasons:

The unit is broken
Units are missing
The unit cannot burn for the complete 90 minutes, which usually indicates the battery life is at its end

Batteries have a wide variety of shelf lives that can range from very short up to ten years. The code does not rely on each manufacturer making the determination, so the code sets three (3) years as the standardized requirement for battery replacement.

Repeated draining and recharging of the battery will shorten its life as well.

Include Exit Lights in Your Annual Fire Protection Service

Call JW Kennedy Fire Protection today.